Sidebar Menu

DISTRIBUTION SYSTEM OVERHEAD CABLE (1000V)

Cat No.:
airdac
Description

Cables for use on urban and rural overhead distribution systems. Cables consist of phase conductors twisted around the neutral messenger made of aluminium alloy Almelec. One or more street lighting conductors may be added to the bundle. Insulation on all conductors. CROSS LINKED POLYETHYLENE (XLPE).

BUNDLE MAIN CHARACTERISTICS TO SABS 1418 - 1986


Bundle Size mm²


Phase    Neutral   Lighting

Bundle

Phase
conductor
approx. Ø

mm

Neutral
conductor
approx. Ø

mm

Lighting
conductor
approx. Ø

mm

Max
current
rating
air at
30°C

3 volt
drop
PF=1.0
at 30°C
V/A/km

Max Liner
resistance
per phase
conductor
at 30°C-km

Approx
overall
Ø
mm

Approx
weight
kg/m

3x25 + 54.6 + 1x25

29

0.70

9

12.4

9

98

2.62

1.200

3x35 + 54.6 + 1x25

31

0.82

10.2

12.4

9

120

1.89

0.868

3x50 + 54.6 + 1x25

33

0.95

11.6

12.4

9

150

1.40

0.641

3x70 + 54.6 + 1x25

37

1.25

13.7

12.4

9

200

0.97

0.443

3x95 + 54.6 + 1x25

41

1.45

15.2

12.4

9

240

0.71

0.320

3x120 + 70 + 1x25

45

1.70

16.5

13.5

9

280

0.57

0.253

3x35 + 35BN

23

0.47

9.65

7.05

N/A

130

1.08

0.868

3x70 + 50BN

30

0.84

11.05

8.05

N/A

205

0.55

0.443

 

 

 

 

 

 

 

 

 

 

 

 

Cable
Description

Size (mm²)

Current Rating
(Amp)

Weight
(kg/m)

2x25

25

98

0.23

4x25

25

92

0.46

2x16AI

16

80

0.15

4x16AI

16

74

0.30

4 Airdac

4-Phase & Neutral,
2.5 Earth

50

0.16

6 Airdac

6-Phase & Neutral,
4 Earth

65

0.22

10 Airdac

10-Phase & Neutral,
7.5 Earth

90

0.32

16 Airdac

16-Phase & Neutral,
10 Earth

125

0.49

4 Airdac II

4

50

0.12

10 Airdac II

10

86

0.25

16 Airdac II

16

125

0.41