Characteristics |
Value |
|
Applicable standards |
IEC 62271-102, IEC 60265 |
|
Rated voltage |
24kV |
36kV |
Impulse withstand voltage Phase-Earth |
125kV |
170kV |
Impulse withstand voltage over isolating distance |
145kV |
195kV |
Power frequency voltage 1 min wet, Phase-Earth |
50kV |
70kV |
Power frequency voltage 1 min wet, over isolating distance |
60kV |
80kV |
Rated frequency |
50 - 60Hz |
50 - 60Hz |
Rated current *) |
630A |
630A |
Short time current |
25kA |
25kA |
Duration of short time current |
3 sec. |
3 sec. |
Peak withstand current |
62,5kA |
62,5kA |
Making capacity |
5kA |
3kA |
Interupting capacity with the loadbreak heads of mainly active load at rated voltage and co =0,7 |
630A |
400A |
Interupting capacity with the loadbreak heads of mainly active load at rated voltage and co =0,15 capacitive |
25A |
16A |
Interupting capacity with the loadbreak heads of mainly active load at rated voltage and co =0,15 reactive |
16A |
4A |
Ringinterupting capacity with the loadbreak heads of mainly active load at rated voltage and co =0,3 reactive |
400A |
400A |
Interupting capacity with breaking whip of mainly active load at rated voltage and co =0,3 reactive |
25A |
16A |
Interupting capacity with breaking whip of cable and line changing currents at rated voltage |
15A |
10A |
Permissable ice load |
Up to 20mm |
|
Mechanical endurance |
>2000 operations |
|
Temperature range |
-50°C to +50°C |
|
Insulator material |
Porcelain, silicon rubber, Outdoor epaxy resin |
|
Insulator creepage distance |
Various of different insulators |